HRN-5 Overvoltage Recorder
A self-contained unit designed for recording of intermittent, atmospheric or switching overvoltage.
Recorder features
- Recording of the time, when equipment voltage exceeded one of five voltage levels
- The individual voltage levels adjustable from 50 % to 600 % of the rated phase voltage of the monitored equipment
- Registering of an overvoltage pulse as short as 1 µs
- Connection of the recording unit
- In low-voltage circuits directly to phase conductors using test leads
- In medium-voltage circuits to capacitive voltage dividers firmly connected to phase conductors
- In high-voltage circuits to diagnostic output of capacitive penetrations of main transformers via an appropriately designed capacitive element
- Capacitive dividers for 6 kV, 24 kV and 400 kV networks are available as accessories
- Original LOGA software for effective data processing, displaying of component state versus time and report printing
- Fully automatic recorder operation
- Robust design suitable for industrial applications
- High reliability

HRN-5 Overvoltage Recorder