Circuit Diagnostics

A regular circuit diagnostics is necessary to prevent electrical equipment failures that may result in significant material losses or personnel injuries.

We perform non-destructive diagnostics of power, control and instrumentation circuits, including cables, connections, penetrations and end devices.

The diagnostic is based on repeated measurements of the following parameters of de-energized circuit:

  • DC and insulation resistance
  • Impedance and phase angle measured at several frequencies
  • Distributed parameters of the circuit using Time Domain Reflectometry (TDR)

It can be applied as a tool of preventive maintenance or for identifying and locating actual failures.

We use ECAD®1000 and ECAD®1100 testing systems produced by CM Technologies Corporation, USA.

Measurement features

  • Connecting of the testing system directly to terminals of the tested circuit
  • Automatic performance of system calibration and diagnostics including measurement of a voltage present at the tested circuit
  • Automatic test performance controlled by a computer
  • Storage of the data acquired during the test in a system database
  • Calculation of AC parameters and factors indicating insulation quality (quality factor, dissipation factor, polarization ration, dielectric absorption ration)
  • Providing comprehensive information of electrical characteristics of the tested circuit
  • Immediate evaluation of the test results by comparison of the acquired data with those of a reference test (the very first test at the same circuit)
  • Estimation of a remaining lifetime based on a long term circuit testing
  • The testing methodology has no adverse effects on the tested circuit